边柱失效的外伸端板连接梁柱子结构抗连续倒塌性能研究

PROGRESSIVE COLLAPSE RESISTANCE OF BEAM-COLUMN SUBSTRUCTURE WITH EXTENDED END PLATE CONNECTION UPON SIDE COLUMN FAILURE

  • 摘要: 为研究钢框架结构边柱失效对其抗连续倒塌性能的影响,制作了两个足尺的钢框架梁柱子结构进行试验研究。通过对试件进行Pushdown加载,研究其抗力机制、内力变化以及破坏模式。结果表明:对于钢框架边跨,边柱失效后形成超长悬臂梁,易由于下翼缘受压而发生整体失稳破坏;设置侧向支撑可使梁破坏模式转变为梁底局部屈曲失效,子结构承载力提高。通过有限元分析研究端板厚度和梁的长度对子结构抗力机制的影响,结果表明:增大端板厚度与缩短钢梁长度均能增大钢梁稳定承载力,提升子结构的抗失稳性能;考虑半刚性节点对钢梁的约束较刚接节点弱,在进行整体稳定承载力计算时需对钢梁计算长度进行修正。利用承载力计算公式计算了不同失效模式下梁柱子结构的承载力,通过与试验及有限元分析结果对比,表明计算结果精度较高。

     

    Abstract: To study the effect of side column failure on collapse resistance of steel frames, two full-scale beam-column substructures were built and tested. The resistance mechanism, internal force change and failure mode of the specimen were studied by pushdown loading tests. For the side span of steel frames, the side column failure forms an ultra-long cantilever beam, which is prone to overall buckling due to compression on the lower flange. Lateral supports can change the failure mode into local buckling of the beam bottom and increase the bearing capacity. The impact of end plate thickness and beam length on the resistance mechanism were investigated by the finite element analysis, which shows that increasing end plate thickness and shortening beam length can enhance anti-instability performance. Considering that the constraint of semi-rigid joints on cantilever beams is weaker than that of rigid joints, the steel beam's calculated length needs adjustment in overall buckling bearing capacity calculations. A bearing capacity calculation model were thusly adopted to calculate the bearing capacity under different failure modes. By comparing the experimental results with finite element analysis ones, the accuracy of the calculation method is verified.

     

/

返回文章
返回